Unit 12.0 kVA
Total Battery 2,365 lbs.
Cabinets (1073 kg)
Electronics 465 lbs.
Cabinet (211 kg)
Total System 2,830 lbs.
(1,284 kg)
L1PH Series Uninterruptible Power Supplies
L1PH
Page 1 of 2 12.0 kVA Single Phase UPS System
Lightolier
a Genlyte Thomas Company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504
Overall Characteristics
86% throughput efficiency
Operating temperature range 32°F (0°C) to 104°F (40°C)
Internal maintenance by-pass is standard
Main load disconnect switch standard
Double conversion, no interruption
Standard backup time of 90 minutes, other run times optional
Output circuit breakers and normally-off loads optional
Housing
Free standing, NEMA 1 enclosure
Acid resistant powder coat finish
Multiple conduit entries
Metering/Controls
Standard
Alpha-numeric front panel display with 14 metered measurements
and 53 messages/alarms
Normal, caution and alarm indicating LEDs
Audible failure alarms with silence switch
Dry contact for remote failure alarm
“D” type 9-pin computer interface connector (see pin config. on back)
Programmable battery monitor with alarm
Optional
Diagnostics software for remote computer (PC) monitoring and control
Stand-alone remote display mimics all measurements, indications
and alarms shown on the front panel display
Additional RS-232 input/output port for remote monitoring and system
control
Electrical
Sine Wave Output
Completely solid-state Pulse Width Modulation (PWM) inverter
16-bit microprocessor control
Input power factor correction maintains power factor at 0.99
Transient response 5%; Recovery time, 10 mS (100% load step)
3:1 crest factor capability
Inverter output distortion 2.5% THD (at unity power factor)
Output voltage regulation ±6% of nominal at full load
Frequency within ±0.05% of nominal
Inverter efficiency 84%
Load power factor capability is 0.5 leading to 0.5 lagging
(Continued on page 2)
Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.
How to Specify:
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
NOTE: Input circuit
breaker not available.
Input switch is
standard.
L1PH I 12.0 S
SERIES INPUT SYSTEM BASE BATTERY OUTPUT OUTPUT # ON 2ND NORMALLY # OF NOL
VOLTAGE TYPE SIZE TYPE VOLTAGE CKT BRKRS
1
VOLTAGE OFF LOAD NOL VOLTAGE
L1PH = Single
Phase
Uninterruptible
Power
Supplies
12.0 = 12.0 kVa
2 = 208 V
3 = 240 V
4 = 277 V
Z = Special
Voltage
(Consult
Factory)
1 = 120 V
2 = 208 V
3 = 240 V
4 = 277 V
5 = 120/208 V
6 = 120/240 V
7 = 120/277 V
Z = Special
Voltage
(Consult
Factory)
Y = Hardwire
A = 1 0CB
B = 2 0CB
C = 3 0CB
D = 4 0CB
E = 5 0CB
F = 6 0CB
G = 7 0CB
H = 8 0CB
J = 9 0CB
K = 10 0CB
L = 11 0CB
M = 12 0CB
N = OCBA1
P = OCBA2
R = OCBA3
S = OCBA4
T = OCBA5
U = OCBA6
V = OCBA7
W = OCBA8
X = OCBA9
0
1
2
3
4
5
6
7
8
9
10
11
A = No
B = Yes
C = Yes w/ Time
Delay Timer
0 = No NOL
Y = Hardwire
Terminal
1 = 1
2 = 2
3 = 3
4 = 4
5 = 5
6 = 6
7 = 7
8 = 8
9 = 9
10 = 10
11 = 11
12 = 12
X = None
A = 1st
B = 2nd
I = ETL Listed
to UL 924 for
Emergency
Lighting
Applications
S = Sealed
Lead Calcium
33.0”
83.8 cm
29.6”
61.0 cm
43.5”
110.5 cm
34.0”
86.4 cm
33.0”
83.8 cm
70.0”
177.8 cm
Battery
Cabinet
Electronics
Cabinet
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - Job Information Type:

Unit 12.0 kVATotal Battery 2,365 lbs.Cabinets (1073 kg)Electronics 465 lbs.Cabinet (211 kg)Total System 2,830 lbs.(1,284 kg)L1PH Series Uninterruptibl

Pagina 2 - AVAILABLE

System Input/Output RatingsWarrantyStandard WarrantyLightolier will provide parts and on-site labor for the first 90 days followingshipment of product

Comentarios a estos manuales